Model Number |
TCS - TCA |
GENERAL FEATURES OF SERIES TCA ?ELECTRIC CONSTRUCTION: Explosionproof Mode of protection EEx-d IIC T6, to std. EN 50.018. Certificate no. CESI 02ATEX118. Degree of protection IP65 (NEMA 4). ?ENCLOSURE: case and cover copper free aluminium alloy, threaded coupling with tamper proof device. Epoxy exterior painting, grey colour. Cable entry: 1/2-14 NPT-F Terminal block: suitable for wires section 1,5 mm2 (minimum 0,5 mm2). Insulating material to VDE standard. Earthing screws: one inside, one outside.Max section of earthing wires: 4 mm2. ?ELECTRIC CONTACTS (see point 1.4 overleaf) One micro, SPDT or DPDT, with fixed dead band. ?SENSOR: vapor tension system to SAMA II C or II A, consisting of -Bulb AISI 316. -Connection AISI 304 compression fitting with adjustable insertion length. -Capillary AISI 316 with stainless steel flexible armor. ?RANGES: -30 to + 250°C, (see point 2 overleaf). ?SET POINT: adjustable throughout the range. Repeatability: better than 1% of span. Scale:the instrument is fitted as std. with an approximate scale of the set point indication. ?MOUNTING: -Direct, sensor type B. -Remote at surface (std.) or 2" pipe (with optional bracket), sensors type C, Q, R. ?AMBIENT TEMPERATURE (operative limits): -20/+60°C. ?EQUIPMENT: certified according to Directive ATEX 94/9/EC Group II Category 2G Annex III+IV
SIL approved
|