GENERAL FEATURES OF SERIES PCS PCA ? ELECTRIC CONSTRUCTION: Explosionproof Mode of protection EEx-d IIC T6, to std. EN 50.018. Certificate no. CESI 02ATEX118. Degree of protection IP65 (NEMA 4). ? ENCLOSURE: case and cover copper free aluminium alloy, threaded coupling with tamper proof device. Epoxy exterior painting, grey colour. Cable entry: 1/2-14 NPT-F. Terminal block: suitable for wires section 1,5 mm2 (minimum 0,5 mm2). Insulating material to VDE standard. Earthing screws: one inside, one outside. Max section of earthing wires: 4 mm2. ? ELECTRIC CONTACTS (see point 1.4 overleaf) One micro, SPDT or DPDT, with fixed dead band. ? SENSOR: P : piston with antagonist spring. G: piston with antagonist spring and seal diaphragm suitable for Category 1/2G or with gas on closed circuits. Wetted parts: see point 2 overleaf. ? RANGES: from 8 bar to 600 bar (see point 2 overleaf). ? SET POINT: adjustable throughout the range. Repeatibility: better than 1% of span. Scale: the instrument is fitted as std. with an approximate scale of the set point indication. ?MOUNTING: -surface or direct (std.), 2" pipe (opt.). ?AMBIENT TEMPERATURE (operative limits): -40/+60°C. ?EQUIPMENT: certified according to Directive PED 97/23/EC Annex I Category IV Modules B+D Directive ATEX 94/9/EC Group II Category 1/2G (PCA_G) Annex III+IV Directive ATEX 94/9/EC Group II Category 2G (PCA_P) Annex III+IV